ABB
ABB
*046W2000UD* Hitachi Energy USA Inc., a subsidiary of Hitachi Ltd.
Alamo, Tennessee
CERTIFIED TEST REPORT
Status: Passed
**

Test Date: 11/19/2024 6:28:42 AM
Apparatus: Condenser Bushing Hitachi Job Number: 1001287390
Bushing Type: O Plus C Hitachi Order Number:
Style: 046W2000UD Version: 6
Rating: 46 kV
BIL: 250 kV
Max L-G Voltage: 29 kV
Serial Number: 2000 Amps (Bottom Connected)
Ambient Temperature: 22 oC Humidity: 25%
  1. Power Factor and Capacitance
    The power factor/capacitance test is conducted per IEEE Std. C57.19.00-2023 & Std. C57.19.01-2017. Test equipment includes a dielectric test set for measurements above 10kV and a dissipation factor/capacitance bridge #428
    Before 60 Hz Withstand
    Measurement Applied kV Power Factor (%) Capacitance (Pfd)
    (C1) Stud to Tap 10 .26 411
    (C2) Tap to Flange 1 NA NA
    Stud to Flange 10
  2. Tap Test: 2 kV 60 Hz one minute applied test, tap to flange: Passed
  3. Dry 60 Hz Withstand and Partial Discharge:
    The tests were conducted per IEEE Std.C57.19.00-2023 & Std. C57.19.01-2017 specifications. The dielectric and partial discharge detection equipment is designed to meet or exceed IEEE 454-1973, C57.113-2023, and C63.2-2023 requirements which includes dividers, detectors, power sources to 1MV, and partial discharge detectors. For units requiring partial discharge in microvolts, tests are conducted per NEMA HV 80036-2026 R2023.
    Start Finish
    Test Voltage (kV) Test Duration (Min) PC PC
    44 NA 2
    125 1 2 2
    44 NA 2
    NA NA
    NA NA
  4. After 60 Hz Withstand (Nameplate information):
    Measurement Applied kV PF% PF%@20C Capacitance (Pfd)
    (C1) Stud to Tap 10 .26 .26 411
    (C2) Tap to Flange 1 .20 .20 427
    Stud to Flange 10
    The pressure and vacuum sealing of this bushing has been verified by testing in accordance with IEEE C57.19.00 - 2023 section 7.4.5. This unit was filled at the factory with PCB-free (non-detectable) dielectric fluid in accordance with U.S. Federal polychlorinated biphenyl (PCB) regulation 40 CFR 61, dated May 31, 1979. The analysis is verified per ASTM-D4059 with a detection level of less than 1 ppm. Bushings are filled with mineral oil that is certified passivator free and certified tested corrosive sulfur free. All tests were conducted on bushings that meet or exceed IEEE C57.19.00-2023
    All dielectric withstand levels for power frequency meet or exceed the routine test levels required by the applicable IEC standards.

Test Specialist: Mateo Sanchez Date: 11/19/2024 6:28:42 AM

Remarks:
*.26* *411* *.20* *427*

Form: CTR-Condenser Bushings/IEEE v1.0 Form Date: 1/1/2000

ABB